Hoshizaki KML "F" SERIES Manuale Utente Pagina 35

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 109
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 34
35
(Control Products HOS-001A Board)
The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position, either the compressor contactor will remain ener-
gized with the control switch OFF, or the unit will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech
Specs book. Number 8 must remain in the OFF position.
Vedere la pagina 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 108 109

Commenti su questo manuale

Nessun commento